Products & Services > Substations > Protection and control systems > VP10 Isolated Relay - Voltage Presence Detection
VP10 Isolated Relay - Voltage Presence Detection
|
The VP10 relay is suited to the detection of DC voltage in power distribution systems for public transport networks.
The VP10 relay, with its high voltage isolation, ensures safety for the equipment and for the personnel.
Main Features
● Adjustable threshold by means of internal dip-switch ● High galvanic isolation up to 10 kV ● Intrinsic safety functioning ● Fuseless solution ● Diagnostic signal |
 |
Technical data
|
Supply voltage
|
3 ranges from 24 to 230 V DC
|
|
Voltage consumption
|
< 5 VA
|
|
Input scale Un
|
1500 or 3000 V DC
|
|
Voltage setting range
|
300-800 or 900-2400 V
|
|
Reset Voltage level
|
< 5 %
|
|
Accuracy
|
+/- 5 % Un
|
|
Trip time delay
|
100 ms (voltage absence)
|
|
Reset time
|
50 ms (voltage presence)
|
|
Output contacts
|
Rating 5 A @ 230 V AC
|
|
Breaking capacity
|
0.3 A @ 110 VDC (DC1)
|
|
Operating temperature
|
-20 ... +70 °C
|
|
Galvanic isolation, input against output
|
10kV AC 50Hz 1min
|
| EMC standards |
EN50124-1
EN 50121-5 (when mounted in a cubicle)
EN 61000-6-2 and EN 61000-6-4
|
Mechanical data
Dimension : 120 x 160 x 92 (H, W, D) Weight : 200 gr Sealing : IP 30 (Housing)
For more information, please e-mail substations@secheron.com or sign up to the Download Center by clicking here.
|