The VP10 relay is suited to the detection of DC voltage in power distribution systems for public transport networks.

The VP10 relay, with its high voltage isolation, ensures safety for the equipment and for the personnel.

 

Main Features

●  Adjustable threshold by means of internal dip-switch
●  High galvanic isolation up to 10 kV
●  Intrinsic safety functioning
●  Fuseless solution
●  Diagnostic signal

 

Technical data

Supply voltage

3 ranges from 24 to 230 V DC

Voltage consumption

< 5 VA

Input scale Un

1500 or 3000 V DC

Voltage setting range

300-800 or 900-2400 V

Reset Voltage level

< 5 %

Accuracy

+/- 5 % Un

Trip time delay

100 ms (voltage absence)

Reset time

50 ms (voltage presence)

Output contacts

Rating 5 A @ 230 V AC

Breaking capacity

0.3 A @ 110 VDC (DC1)

Operating temperature

-20 ... +70 °C

Galvanic isolation, input against output  

10kV AC 50Hz 1min

EMC standards

EN50124-1

EN 50121-5 (when mounted in a cubicle)

EN 61000-6-2 and EN 61000-6-4

Mechanical data

Dimension  : 120 x 160 x 92 (H, W, D)
Weight  : 200 gr
Sealing : IP 30 (Housing)

 

For more information, please e-mail substations@secheron.com or sign up to the Download Center by clicking here.